Model
|
SUN-20K
-SG01HP3-EU |
SUN-25K
-SG01HP3-EU |
SUN-30K
-SG01HP3-EU |
SUN-40K
-SG01HP3-EU |
SUN-50K
-SG01HP3-EU |
Battery Input Data
|
|||||
Battery Type
|
Lead-acid or Lithium-ion
|
||||
Battery Voltage Range(V)
|
200~700
|
||||
Max. Charging Current (A)
|
37
|
37+37
|
|||
Max. Discharging Current (A)
|
37
|
37+37
|
|||
Number of battery input
|
1
|
2
|
|||
Charging Curve
|
3 Stages / Equalization
|
||||
Charging Strategy for Li-Ion Battery
|
Self-adaption to BMS
|
||||
PV String Input Data
|
|||||
Max. DC Input Power (W)
|
26000
|
32500
|
39000
|
52000
|
65000
|
Max. DC Input Voltage (V)
|
1000
|
||||
Start-up Voltage (V)
|
160
|
||||
MPPT Range (V)
|
200~850
|
||||
Full Load DC Voltage Range (V)
|
360-850
|
365-850
|
435-850
|
450-850
|
450-850
|
Rated DC Input Voltage (V)
|
500
|
625
|
500
|
500
|
625
|
PV Input Current (A)
|
36+36
|
36+36+36
|
36+36+36+36
|
||
Max. PV ISC (A)
|
50+50
|
50+50+50
|
50+50+50+50
|
||
Number of MPPT / Strings per MPPT
|
2/2+2
|
3/2+2+2
|
4/2+2+2+2
|
||
AC Output Data
|
|||||
Rated AC Output and UPS Power (W)
|
20000
|
25000
|
30000
|
40000
|
50000
|
Max. AC Output Power (W)
|
22000
|
27500
|
33000
|
44000
|
55000
|
Peak Power (off grid)
|
2 times of rated power, 10 S
|
||||
AC Output Rated Current (A)
|
30.3
|
38
|
45.6
|
60.8
|
75.8
|
Max. AC Current (A)
|
45.4
|
41.8
|
50.1
|
66.9
|
83.3
|
Max. Continuous AC Passthrough (A)
|
100
|
||||
Generator input/Smart load
/AC couple current (A) |
30.3 / *180 / 30.3
|
38 / *180 / 38
|
45.6 / *180 / 45.6
|
60.8 / *180 / 60.8
|
75.8 / *180 / 75.8
|
Power Factor
|
0.8 leading to 0.8 lagging
|
||||
Output Frequency and Voltage
|
50/60Hz; 3L/N/PE 220/380, 230/400Vac
|
||||
Grid Type
|
Three Phase
|
||||
DC injection current (mA)
|
<0.5%1n
|
||||
Efficiency
|
|||||
Max. Efficiency
|
97.60%
|
||||
Euro Efficiency
|
97.00%
|
||||
MPPT Efficiency
|
99.90%
|
||||
Protection
|
|||||
Integrated
|
PV Input Lightning Protection, Anti-islanding Protection, PV String Input Reverse Polarity Protection,Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection,Surge protection
|
||||
Certififications and Standards
|
|||||
Grid Regulation
|
EN50549, AS4777.2, VDE0126, IEC61727, VDEN4105, G99, NBT32004, CEI0-21, NRS097,NBR16149/16150, RD1699
|
||||
Safety EMC / Standard
|
IEC62109-1/-2, EN61000-6-1, EN61000-6-2, EN61000-6-3, EN61000-6-4
|
||||
General Data
|
|||||
Operating Temperature Range (℃)
|
-45~60℃, >45℃ derating
|
||||
Cooling
|
Smart cooling
|
||||
Noise (dB)
|
<45 dB
|
||||
Communication with BMS
|
RS485; CAN
|
||||
Weight (kg)
|
60
|
||||
Size (mm)
|
560.5W×837H×319D
|
||||
Protection Degree
|
IP65
|
||||
Installation Style
|
Wall-mounted
|
||||
Warranty
|